Appendix C: SRX5400 Services Gateway Power Guidelines, Requirements, and Specifications
To ground the services gateway, you must connect a grounding cable to earth ground
and then attach it to the chassis grounding point using the two screws provided.
NOTE:
Additional grounding is provided to an AC-powered services gateway
when you plug its power supplies into grounded AC power receptacles.
SRX5400 Services Gateway Grounding-Cable Lug Specification on page 193
SRX5400 Services Gateway Grounding-Cable Specification on page 193
The accessory box shipped with the services gateway includes the cable lug that attaches
to the grounding cable (see
secure the grounding cable to the grounding points.
Figure 67: Grounding Cable Lug
CAUTION:
Before services gateway installation begins, a licensed electrician
must attach a cable lug to the grounding and power cables that you supply.
A cable with an incorrectly attached lug can damage the services gateway.
NOTE:
The same cable lug is used for the DC power cables.
SRX5400 Services Gateway Chassis Grounding Point Specifications on page 192
SRX5400 Services Gateway Grounding-Cable Specification on page 193
The grounding cable that you provide must meet the specifications in
Table 28: Grounding Cable Specifications
Cable Type
Grounding
Figure 67 on page
193) and two UNC 1/4–20 screws used to
Quantity and Specification
2
One 6-AWG (13.3 mm
), minimum 60°C wire, or as required by
the local code
Table 28 on page
193.
193