Juniper SRX5400 Hardware Manual page 212

Services gateway
Hide thumbs Also See for SRX5400:
Table of Contents

Advertisement

SRX5400 Services Gateway Hardware Guide
Table 32: DC Power Supply Electrical Specifications (continued)
Item
DC input current rating
Internal Supplementary Protector
Table 33: DC Power System Specifications
Item
Redundancy
Output power (maximum) per power supply
Output power (maximum) per system
Related
Documentation
DC Power Circuit Breaker Requirements for the SRX5400 Services Gateway
Related
Documentation
198
Specification
DIP=0 (60 A Input)
50 A @ –48 V nominal operating voltage
None
Specification
DIP=0 (60 W Input)
2+2
2400 W
4800 W
Calculating Power Requirements for the SRX5400 Services Gateway on page 189
DC Power Circuit Breaker Requirements for the SRX5400 Services Gateway on page 198
DC Power Source Cabling for the SRX5400 Services Gateway on page 199
DC Power Cable Specifications for the SRX5400 Services Gateway on page 200
DC Power Cable Lug Specifications for the SRX5400 Services Gateway on page 200
Each DC power supply has a single DC input (–48 VDC and return) that requires a
dedicated facility circuit breaker. We recommend that you use a customer site circuit
breaker rated for 40 A (–48 VDC) minimum for each DC power supply, or as required by
local code. Doing so enables you to operate the services gateway in any configuration
without upgrading the power infrastructure.
If you plan to operate a DC-powered services gateway at less than the maximum
configuration and do not provision a 40 A (–48 VDC) circuit breaker, we recommend
that you provision a circuit breaker for each DC power supply rated for at least 125% of
the continuous current that the system draws at –48 VDC, or as required by local code.
Calculating Power Requirements for the SRX5400 Services Gateway on page 189
SRX5400 Services Gateway DC Power Supply Specifications on page 197
DC Power Source Cabling for the SRX5400 Services Gateway on page 199
DC Power Cable Specifications for the SRX5400 Services Gateway on page 200
DIP=1 (70 A Input)
54.2 A @ –48 V nominal operating
voltage
None
DIP=1 (70 W Input)
2+2
2600 W
5200 W
Copyright © 2014, Juniper Networks, Inc.