Mitsubishi Electric MELSEC iQ-R Series User Manual page 563

Motion module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Error
Error
Error name
code
(System/
(Hexad
axis/axes
ecimal)
group)
350BH
System
END Instruction Error
350CH
System
Program Execution
Error
350DH
System
Insufficient Memory
Capacity
350EH
System
FB FUN Program Error
350FH
System
Operation Error
3510H
System
Device/Label
Specification Incorrect
3511H
System
FB FUN Execution
Error
3512H
System
Parameter Error
3513H
System
Parameter Error
3514H
System
Program Error
Error detail and cause
Detection
timing (At
start/
during
control
The END (FEND) instruction
At ready ON
does not exist in the program.
• After the global label setting file
At ready ON
was modified, only the global
label setting was written. Or,
after the global label setting
was modified, only the program
and FB/FUN were written. (The
global label setting file was not
written.)
• After the FB/FUN was
modified, only the FB/FUN was
written. Or, after the FB/FUN
was modified, only the program
and global label setting were
written. (The FB/FUN was not
written.)
• After the buffer memory refresh
setting of the global label
setting was modified, only the
program and FB/FUN were
written to PLC. (The global
label setting file was not
written.)
Insufficient capacity of program
At ready ON
storage target.
FB/FUN program configuration is
At ready ON
incorrect.
The link direct device or buffer
At ready ON
memory access device is
specified for both (s) and (d) used
in the BMOV instruction.
• The device or label specified in
At ready ON
the instruction exceeded the
usable range.
• Array was not selected.
Before the FB/FUN program
At ready ON
ends, the call source program
ended.
The fixed scan program interval
At ready ON
exceeded 16 kinds.
• The incorrect execution type
At ready ON
has been specified.
• The incorrect execution
condition has been specified.
The execution type that cannot
During END
be changed has been specified.
processing
Operation at
Remedy
error
occurrence
The program stops.
• Please check the
corresponding
program, and correct
it.
• Please write the
program and FB
program again.
The program stops.
Please write the
program, FB/FUN and
global label setting.
The program stops.
Please check the
memory capacity of ST
addon.
The program stops.
• Please check the
corresponding file,
and correct it.
• Please write the
program and FB/FUN
again.
The program stops.
Please check the BMOV
instruction of
corresponding file, and
correct it.
The program stops.
Please check the
corresponding file, and
correct it.
The program stops.
• Please check the
corresponding file,
and correct it.
• Please write the
program and FB/FUN
again.
The program stops.
Please set the fixed scan
program interval within
16 kinds.
The program stops.
• Please change to a
correct execution type.
• Please check the fixed
scan interval.
The program stops.
Please specify the
execution type that can
be changed.
22 TROUBLESHOOTING
22.5 List of Error Codes
22
561

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rd78g32Rd78g64Rd78ghvRd78g4Rd78ghwRd78g8 ... Show all