Error
Error
code
(System/
(Hexad
axis/axes
ecimal)
group)
1AADH
Axis
1AAEH
Axis
1AAFH
Axis
1AB0H
Axis
1AB1H
Axis
1AB2H
Axis
1AB3H
Axis
1AB4H
Axis/Axes
group
1AB5H
Axis
1AB6H
Axis
22 TROUBLESHOOTING
544
22.5 List of Error Codes
Error name
Error detail and cause
Start Not Possible
Positioning start not possible.
• Moderate Error Detected
(Detail Code: 0001H)
• PLC Ready OFF (Detail Code:
0002H)
• Forced Stop Signal ON (Detail
Code: 0003H)
• Axis Stop Signal ON (Detail
Code: 0004H)
• Axis/Axis Group Status
Incorrect (Detail Code: 0100H)
• Axis Group Operating (Detail
Code: 0101H)
• Configuration Axis Status
Incorrect (Detail Code: 0102H)
Driver Error
An error occurred in the driver.
Driver Ready OFF
Driver power OFF during
controlling.
• Driver power is OFF
• Initial processing when driver
power is ON
• The driver is not installed
• Driver error occurs
PLC READY OFF
PLC READY signal [Y0] was
During Operation
turned OFF during operation.
CPU Error During
System error was detected during
Operation
operation.
Driver Network
Driver network disconnection was
Disconnection
detected during operation.
Executing FB Analysis
An error was detected in
Disabled
executing FB analysis at target
changing position.
Buffering FB Analysis
An error was detected in the
Disabled
buffering FB analysis.
Ring Counter Invalid
Ring counter setting was started
Start
in the invalid status.
External Signal String
Incorrect string was set in the
Incorrect
string of external signal.
Detection
Operation at
timing (At
error
start/
occurrence
during
control
At start
Not start.
During
Stops immediately.
operation
During
Stops immediately.
operation
During
Stops the operation.
operation
During
Stops the operation.
operation
During
Stops immediately.
operation
At control
Stops the operation.
change
During
Stops the operation.
operation
At start
Not start.
At start
Not start.
Remedy
• Set it so that it will not
start when PLC
READY is OFF.
• Set it so that it will not
start when READY is
OFF.
• Check the sequence
program of which PLC
READY signal [Y0] is
ON/OFF.
• Check the drive
module power status,
wiring and connector
connection status with
drive module.
• Start it after
transferring
"AxesGroupName.Md.
GroupStatus" to
"GroupStandby".
• Start it after
transferring
"AxisName.Md.AxisSt
atus" to "StandStill".
Please check the error
details and corrective
action for
"AxisName.Md.DriverErr
orID". (Please refer to
the each driver
instruction manual for
"AxisName.Md.DriverErr
orID" details.)
Please turn on the power
supply of driver.
Check the sequence
program of which PLC
READY signal [Y0] is
ON/OFF.
Please turn the module
power on again.
lease check the
connection cable of
driver.
Change the target
position so that the
executing FB analysis
will not result in an error.
Set buffering FB analysis
so that it will not result in
an error.
Enable the
"AxisName.PrConst.Rin
gCount_Enable".
Set the valid string in the
external signal.