Relevant variables

Variable/Structure name
*1
System.LoggingRef[1..10].Cd.
SettingPath
StartLog
Trigger
*1
System.LoggingRef[1..10].Md.
SettingPath
LogDataPath
LoggingStatus
Triggered
TriggerCount
TrigerCountIgnored
LogDataSavedCount
TriggerStatus[1..32]
SaveStatus
LogType
ErrStatus
SamplingTime[0..1]
System.PrConst.
Logging_AutoLoggingEnable
*1 The array elements [1] to [10] correspond to the logging setting 1 to 10.
Name
Logging setting path
Logging request
Trigger request
Logging setting file
Logging data file path
Logging status
Triggered
Trigger detection count
Trigger ignored count
Number of saved files
Trigger status
Save status
Logging type
Error status
Data collection interval
Auto logging enabled
Details
Sets the storage location path (folder name/file name) of logging setting.
Requests the execution of logging.
FALSE: STOP
TRUE: RUN
Requests the trigger when "Trigger command" is set for a trigger condition.
FALSE: No request
TRUE: Request
Indicates the path (file name) of the logging setting file during the logging.
Indicates the path (file name) of the logging data file.
Indicates the logging execution status.
FALSE: Stop
TRUE: Executing
Indicates the triggered status.
Indicates the trigger detection count.
A trigger occurs again during collecting data after trigger and it indicates the
trigger ignored count.
Indicates the number of saved data logging files.
Indicates the status of each trigger condition.
FALSE: Trigger condition not established
TRUE: Trigger condition established
Indicates the save status to files of collected data.
0: UnSave (Unsaved)
1: Saving (Saving)
2: Saved (Saved)
3: FullySaved (Fully saved)
Indicates the logging type in progress.
Stores the error code related to logging.
Indicates the data collection interval in a unit of ns.
[0] Sampling interval lower 32 bits
[1] Sampling interval upper 32 bits
Enables auto logging function. Auto logging can be executed only when the
logging setting file is stored in the SD memory card.
FALSE: Disabled
TRUE: Enabled
15.1 Data Logging/Real-Time Monitor
15
15 LOGGING