22 TROUBLESHOOTING
550
22.5 List of Error Codes
Error name
Error detail and cause
File Access Error
The following operations was
attempted in the engineering tool
and SLMP path.
• An access (read/write) from
other request source to written
file was operated.
• A write from other request
source to access (read/write)
file was operated.
WDT Error Detected
• System memory setting
WDT error when the memory
was not secured in function
that influences control.
• Programming
It exceeded 2.0 [s] from
executing start to executing
end. (Initial execution type)
The operation time of all
normal operation type program
exceeded 1.0 [s].
• Execution Time monitor
WDT error will be detected
after one second when
calculation processing and
other processing are abnormal
and processing stops.
AddOn Library Load
AddOn
Error
• The file of AddOn is broken.
• AddOn with dependencies has
not been installed.
• AddOn that cannot be
combined has been installed.
• Inconsistency occurred in
versions.
Drive Error
• Mount of driver failed
• Check disk error ended
• The verification of disk
management target error
Insufficient Total
The total number of
System Memory (RAM)
System.PrConst.Addon_AddonLi
braryName.RamSizeMax for
each addon exceeds the total
size of system memory (RAM).
Detection
Operation at
timing (At
error
start/
occurrence
during
control
When
Fails to access the files.
accessing file
During
The axis in operation
operation
stops immediately.
At power ON
AddOn
The motion system does
not start.
At system
Access to the target
start
drive is not allowed.
At power ON
The motion system does
not starts.
Remedy
Please operate the next
access after one process
of request source is
completed.
• System memory
setting
Increase
System.PrConst.Addo
n_AddonLibraryName.
RamSizeMax or
System.PrConst.Addo
n_AddonLibraryName.
BackUpRamSizeMax.
• Programming
Reduce the number of
command execution of
initial execution type
and normal execution
type by program.
• Execution Time
monitor
Change the system
basic cycle, the first
calculation cycle, and
buffer memory refresh
cycle to a larger value.
Change the fixed scan
interval setting of fixed
scan execution type
program to a larger
value.
AddOn
• Please install the
software again.
• Please install the
AddOn with
dependencies.
• Please delete the
AddOn that cannot be
combined.
• Please uninstall or
delete the AddOn that
inconsistency
occurred in versions.
Format Target Drive.
Please set the total
number of
System.PrConst.Addon_
AddonLibraryName.Ram
SizeMax for each addon
so that it does not
exceed the total size of
system memory (RAM).