8-6 Extended Parameters
Pn512
Overload Detection Level Setting
Setting
0 to 500
range
 Set the overload detection level.
If this setting is 0, the level is set to 115% of nominal torque
Internally there is a limit of 115%, so higher values are limited to 115%
This object is set as a percentage of the rated torque.
Pn513
Overspeed Detection Level Setting
Setting
0 to 20,000
range
 Set the overspeed detection level.
The overspeed detection level setting is 1.2 times the maximum motor rotation speed if this
parameter is set to 0.
This parameter should normally be set to 0. The setting should be changed only when it is
necessary to lower the overspeed detection level.
The set value of this parameter is limited to 1.2 times the maximum motor rotation speed.
The detection margin of error for the set value is ±3 r/min for 17 bit absolute encoder and ±36 r/
min for a 20 bit incremental encoder
Pn514
Overrun Limit Setting
Setting
0 to 1,000
range
 Set the allowable operating range for the position command input range.
If the set value is exceeded, motor operation range setting protection is activated.
8
When position command is not input
When position command is input
Pn515
Control Input Signal Read Setting
Setting
0 to 3
range
8-53
Unit
Unit
Unit
Motor
Load
Pn514 Pn514
Servomotor's allowable
Alarm generation range
operating range
Motor
Pn514
Alarm generation range
Unit
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Default
%
setting
Default
r/min
setting
Default
0.1 rotation
setting
Alarm generation range
Load
Position command
Pn514
input range
Servomotor's allowable
Alarm generation range
operating range
Default
setting
All
Power OFF
0
and ON
All
Power OFF
0
and ON
Position Fully-closed
Power OFF
10
and ON
All
Power OFF
0
Yes
and ON