6-9 Sequence I/O Signal
 Do not use any values other than the settings listed.
 If you allocate the same function to multiple input signals, interface input duplicate allocation error
1 (Alarm 33.0) or interface input duplicate allocation error 2 (Alarm 33.1) will occur.
 You can allocate error counter reset input (ECRST) to Input Signal Selection 7 (Pn406) only. If
you allocate it to anything other than that, a counter reset allocation error (Alarm 33.6) will occur.
 You can allocate pulse prohibition input (IPG) to Input Signal Selection 10 (Pn409) only. If you allocate
it to anything other than that, a command pulse prohibition input allocation error (Alarm 33.7) will
occur.
 If you are using the control mode switching input (TVSEL), you must set it for all control mode. If
you do not set it for all control mode, interface input function number error 1 (Alarm 33.2) or
interface input function number error 2 (Alarm 33.3) will occur.
 If you set Zero Speed Designation Selection (Pn315) to 2 or 3, you must always allocate zero
speed designation input (VZERO) in speed control for the same pin where zero speed designation
input (VZERO) is allocated for speed control. In addition, specify the same settings for the logic.
 Be sure to allocate the functions that are used by multiple control mode (such as operation command and
alarm reset input) to the same pin, and do the same for the logic. If this is not set correctly, interface input
duplicate allocation error 1 (Alarm 33.0) or interface input duplicate allocation error 2 (Alarm 33.1) will
occur.
 You must always allocate the operation command (RUN). Servo cannot be turned ON if it is not
allocated.
6
Output Signals
You can allocate output signal functions to the output pins for the control I/O connector (CN1).
If a G-series Servo Drive is being replaced with a G5-series Servo Drive, use the G5-series
Servo Drive with the default settings.
Output Signal Default Setting
The allocations of the default output signals are as follows. Refer to "Output Signal Allocation
Method" when you change the allocation to use.
Applicable
parameters
Pn410
Pn411
Pn412
Pn413
*1 Alarm output signal allocations cannot be changed.
6-38
Precautions for Correct Use
Output
Default set
Signals
value
SO1
00030303h
output
(197379)
SO2
00020202h
output
(131586)
SO3
*1
output
SO4
00050504h
output
(328964)
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
Default setting state
Position control
or fully-closed
Speed control
control
Signal name
Signal name
BKIR
BKIR
READY
READY
ALM
ALM
INP
TGON
Torque control
Signal name
BKIR
READY
ALM
TGON