Power Ratings; Power Ratings; Three-Phase 208 Vac Models Z1B1D002 To D046 - YASKAWA Z1000 Technical Manual

Ac drive bypass for hvac fans and pumps 208 v: 1/2 to 100 hp 480 v: 3/4 to 250 hp
Hide thumbs Also See for Z1000:
Table of Contents

Advertisement

A.1 Power Ratings
A.1 Power Ratings
u

Three-Phase 208 Vac Models Z1B1D002 to D046

Item
Bypass Model Z1B1
Maximum
Applicable
Motor
<1>
Capacity
Input Current (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Rated Output Current (A)
Overload Tolerance
Output
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Harmonics
DC Link Choke
Reduction
EMC
Filter (IEC/EN 61800-3 Category 2)
<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or
greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Carrier frequency is set to 5 kHz. Current derating is required to raise the carrier frequency.
300
Table A.1 Power Ratings (Three-Phase 208 V)
D002
HP
0.5
kW
0.37
<2>
2.9
<3>
2.4
YASKAWA ELECTRIC SIEP YAIZ1B 01E YASKAWA AC Drive – Z1000 Bypass Technical Manual
Specification
D003
D004
D007
0.75
1
2
0.55
0.74
1.5
4.0
5.1
8.0
Three-phase 208 Vac 50/60 Hz
-15 to 10%
<3>
<3>
<3>
3.5
4.6
7.5
110% of rated output current for 60 s
150% peak
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Three-phase 208 Vac
D010
D016
D024
3
5
7.5
2.2
3.7
5.5
11.1
17.2
24.7
±5%
<3>
<3>
<3>
10.6
16.7
24.2
240 Hz
Built-in
Built-in
D030
D046
10
15
7.5
11
31.3
46.7
<3>
<3>
30.8
46.2