A.2 Power Ratings
u

Three-Phase 200 V Class Drive Models 2o0028 to 2o0081

Maximum Applicable
Motor Capacity kW (HP)
Rated Input Current (A)
Rated Input Capacity (kVA)
Input/
Rated Output Current (A)
Output
Rating
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
Power
Allowable Voltage Fluctuation
Supply
Allowable Frequency Fluctuation
Allowable Phase Power Supply Voltage Unbalance
Harmonic Current Distortion
Input Power Factor
<1> The motor capacity (HP) refers to an NEC 4-pole motor. The rated output current of the drive should be equal to or greater than the motor current.
Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 240 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.
<6> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Table A.2 Power Ratings (Three-Phase 200 V Class)
Item
Drive Model
HD Rating
<1>
ND Rating
HD Rating
<2>
ND Rating
HD Rating
<3>
ND Rating
HD Rating
<4> <5>
ND Rating
Overload Tolerance
Carrier Frequency
Rated Voltage
Rated Frequency
<6>
Specification
2o0028
2o0042
2o0054
5.5 (7.5)
7.5 (10)
7.5 (10)
11 (15)
20
25
25
38
9
12
12
17
22
28
28
42
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Proportional to input voltage
400 Hz (User-adjustable)
Three-phase 200 to 240 Vac 50/60 Hz
-15 to 10%
±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
2% or less
5% or less (IEEE519 compliant)
0.98 or more (During rated operation)
A.2 Power Ratings
2o0068
2o0081
11 (15)
15 (20)
18.5 (25)
15 (20)
18.5 (25)
22 (30)
38
49
49
62
17
22
22
28
42
54
54
68
<6>
62
74
28
34
68
81
A