DC Power Grounding Requirements and Warning

254
Aviso Antes de executar um dos seguintes procedimentos, certifique-se que
desligou a fonte de alimentação de energia do circuito de corrente contínua.
Para se assegurar que toda a corrente foi DESLIGADA, localize o disjuntor no
painel que serve o circuito de corrente contínua e coloque-o na posição OFF
(Desligado), segurando nessa posição a manivela do interruptor do disjuntor
com fita isoladora.
¡Atención! Antes de proceder con los siguientes pasos, comprobar que la
alimentación del circuito de corriente continua (CC) esté cortada (OFF). Para
asegurarse de que toda la alimentación esté cortada (OFF), localizar el
interruptor automático en el panel que alimenta al circuito de corriente
continua, cambiar el interruptor automático a la posición de Apagado (OFF),
y sujetar con cinta la palanca del interruptor automático en posición de
Apagado (OFF).
Varning! Innan du utför någon av följande procedurer måste du kontrollera
att strömförsörjningen till likströmskretsen är bruten. Kontrollera att all
strömförsörjning är BRUTEN genom att slå AV det överspänningsskydd som
skyddar likströmskretsen och tejpa fast överspänningsskyddets omkopplare
i FRÅN-läget.
General Safety Guidelines and Warnings on page 211
General Electrical Safety Guidelines and Warnings on page 243
DC Power Electrical Safety Guidelines on page 250
DC Power Grounding Requirements and Warning on page 254
DC Power Wiring Sequence Warning on page 255
DC Power Wiring Terminations Warning on page 257
This topic applies to hardware devices in the EX Series product family, which includes
EX Series switches and the XRE200 External Routing Engine.
This topic also applies to hardware devices in the QFX Series and to OCX1100 switches.
An insulated grounding conductor that is identical in size to the grounded and ungrounded
branch circuit supply conductors but is identifiable by green and yellow stripes is installed
as part of the branch circuit that supplies the device. The grounding conductor is a
separately derived system at the supply transformer or motor generator set.
WARNING:
When you install the device, the ground connection must always
be made first and disconnected last.
Copyright © 2016, Juniper Networks, Inc.