Figure 16: Clearance Requirements For Airflow And Hardware Maintenance For Ex2200 Switches Except Ex2200-C Switch Models; Figure 17: Clearance Requirements For Airflow And Hardware Maintenance For - Juniper EX2200 Hardware Manual

Hide thumbs Also See for EX2200:
Table of Contents

Advertisement

Copyright © 2016, Juniper Networks, Inc.
Figure 16: Clearance Requirements for Airflow and Hardware Maintenance
for EX2200 Switches Except EX2200-C Switch Models
24" (61 cm)
Clearance required
for maintenance
Front
17.5"
44.5 cm
Mounting bracket
Figure 17: Clearance Requirements for Airflow and Hardware Maintenance
for EX2200-C Switch Models
24" (61 cm)
Clearance required
for maintenance
Front
7.18"
(26.9 cm)
Mounting bracket
The power cord retainer clips extend out of the rear of the chassis by 3 in.
Allow at least 6 in. (15.2 cm) of clearance on the side between devices that have fans
or blowers installed. Allow 2.8 in. (7 cm) between the side of the chassis and any
non-heat-producing surface such as a wall. For the cooling system to function properly,
the airflow around the chassis must be unrestricted.
Figure 18 on page 60
shows the airflow in PoE models of EX2200 switches, except for
EX2200-C models.
Figure 19 on page 60
switches, except for EX2200-C models.
24" (61 cm)
6" (15.2 cm)
Clearance required
for airflow
for maintenance
Rear
10.5"
19"
(26.7 cm)
(48.2 cm)
6" (15.2 cm)
for airflow
6" (15.2 cm)
6" (15.2 cm)
for airflow
8.7"
19"
(22.1 cm)
(48.2 cm)
6" (15.2 cm)
for airflow
shows the airflow non-PoE models of EX2200
Chapter 6: Preparation Overview
Clearance
required for
maintenance
Rear
59

Advertisement