"Minimum switch-on" - minimum time for
which the DX cooler is to remain switched on
after it has been switched on
•
"Minimum shutdown" - minimum time for
which the DX cooler is to remain off after it
has been switched off
•
"Start-up interval" - minimum time between
DX cooler activations
•
"Operation
blocking"
operating modes for which the operation of
the DX cooler is blocked
•
"Stage 1 - Start" - minimum controller
control from which the first stage of the DX
cooler starts, if it was off
•
"Stage 1 - Stop" - controller control at which
the first stage of the DX cooler is switched
off, if it was switched on
•
"Stage 2 - Start" - minimum controller
control from which the second stage of the
DX cooler starts, if it was switched off
•
"Stage 2 - Stop" - controller control at which
the second stage of the DX cooler is
switched off, if it was switched on
•
"Actuator signal" - the control voltage of
the radiator valve actuator to which the zero
adjustment corresponds (e.g. for 2-10V
controlled actuators, set 20% so that 0% of
the controller output signal corresponds to
2V control voltage)
-