BASIC FACTORY CONFIGURATION - OPERATING PROFILES (MODE)
PARAMETER
Temperature
Relative humidity - RH
Air quality - CO2 content
Supply capacity
Exhaust capacity
•
Work profiles: Comfort, Economic require the time and date of their validity to be set in the
calendar.
•
Standby operating profile - requires parameter setting:
o
Standby time, i.e. the minimum time for which the AHU is awakened in StandBy mode,
o
Wake-up time, i.e. the time determining the interval between automatic wake-ups of the
AHU in StandBy mode.
•
* - humidity control requires the unit to be equipped with humidification and dehumidification
functions, otherwise the values are read-only,
•
** - 100% means the capacity from the selection sheet.
www.vtsgroup.com
°C
T
RH*
%
ppm
ppm
V *
% m3/h
S
V *
% m3/h
E
OIMM VENTUS COMPACT - ver. 6.0.0 (06.2024)
WORK PROFILES
Comfort**
Economic
Comfort**
Ekono
22
22
50
50
600
900
100
60
100
60
StandBy
StandBy
22
50
900
60
60
61