VTS Medical Systems VENTUS COMPACT VVS021c Instructions For Use Manual page 108

Compact air handling units
Hide thumbs Also See for VENTUS COMPACT VVS021c:
Table of Contents

Advertisement

F04
www.vtsgroup.com
OIMM VENTUS COMPACT - ver. 6.0.0 (06.2024)
- dew point" - temperature after the
"Supply
recovery on the supply air (sensor B6), the
maintenance of which will be carried out by
the PID controller of the dew point
compensation in case it drops (supply air
humidity transmitter is mainly used in cases
of AHUs equipped with a humidifier)
"PID control signal" - current control of the
dew point compensation PID controller
"Delta dew point" - permissible deviation of
the temperature after recovery in the supply
air relative to the temperature after recovery
in the exhaust air (sensor B4), below which
the dew point compensation PID controller is
inactive
"Kp" - gain factor of the dew point
compensation PID controller
"Ti" - dew point compensation PID controller
doubling time
108