The Most Common Adaptations Of Parameters To The Needs Of The Facility - VTS Medical Systems VENTUS COMPACT VVS021c Instructions For Use Manual

Compact air handling units
Hide thumbs Also See for VENTUS COMPACT VVS021c:
Table of Contents

Advertisement

7.2.9
THE MOST COMMON ADAPTATIONS OF PARAMETERS TO THE NEEDS
OF THE FACILITY
FUNCTION
SCREEN
MAIN HEATER
DXH MAINTAIN
SECONDARY
HEATER
PRE-HEATER
MAIN RADIATOR
DX MAINTAIN
VENTILATORS
VENTILATORS
RECOVERY
DEVICE
RECOVERY
DEVICE
MIXING CHAMBER
MIXING CHAMBER
GENERAL
VENTILATORS
GENERAL
GENERAL
GENERAL
N VENTILATORS
FANS W
CO2
VENTILATORS
VENTILATORS
MIXING CHAMBER
MIXING CHAMBER
HUMIDIFIER
BED HUMIDIFIER
GENERAL
HMI BASIC
DXH MAINTAIN
DXH
INTRODUCTION
DXH
INTRODUCTION
www.vtsgroup.com
SCOPE OF THE
CHANGES
A07
PID
compressor switch-on
A11
thresholds
A12
PID
PID, post-heat temp.
A16
settings, min/max power
B03
PID, min/max power
compressor switch-on
B05
thresholds
C16
PID
setting of capacity
C16
dependence on temp. reg.
D02
PID, min/max power
D03
PID
E02
PID in the heating direction
E03
PID in cooling direction
min/max temp, min/max
H01
temp setting
PID efficiency depending on
H02
temp. reg.
heating/cooling switchover
H03
thresholds
H04
StdBy" mode parameters
selection of the leading
I02
temperature
C07
PID`
C08
PID
C12
PID
setting the performance
C12
relationship to the CO2 reg.
E04
PID
parameters of the "rapid
E06
heating" function
F02
PID
F03
humidifier on/off threshold
selection of the leading
I02
moisture content
Sensor activation in the HMI
I05
Basic
A10
compressor run-time setting
A14
compressor run-time setting
A18
compressor run-time setting
OIMM VENTUS COMPACT - ver. 6.0.0 (06.2024)
WHEN TO CHANGE
unstable temperature control
unstable temperature control
unstable temperature control
unstable temperature control
unstable temperature control
unstable temperature control
unstable temp. control
matching of object properties
unstable temperature control with heat
recovery
unstable temperature control with
cooling recovery
Unstable temperature control with
inefficient heat source
Unstable temperature control with
inefficient heat source
matching of object properties
unstable regulation of performance on
temperature
unstable temperature control
matching of object properties
matching of object properties
unstable capacity regulation
unstable capacity regulation
unstable co2 control by changing output
matching of object properties
unstable co2 control by changing
recirculation
matching of object properties
unstable humidity control
unstable or inaccurate humidity control
matching of object properties
adaptation to the needs of the site
85