Connecting The Measuring Device: Proline 500 - Digital; Connecting The Connecting Cable - Endress+Hauser Proline Promass E 500 PROFINET Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass E 500 PROFINET
Endress+Hauser
7.2
Connecting the measuring device: Proline 500 -
digital
NOTICE
Limitation of electrical safety due to incorrect connection!
Have electrical connection work carried out by appropriately trained specialists only.
Observe applicable federal/national installation codes and regulations.
Comply with local workplace safety regulations.
Always connect the protective ground cable  before connecting additional cables.
For use in potentially explosive atmospheres, observe the information in the device-
specific Ex documentation.
7.2.1

Connecting the connecting cable

WARNING
L
Risk of damaging the electronic components!
Connect the sensor and transmitter to the same potential equalization.
Only connect the sensor to a transmitter with the same serial number.
Ground the connection housing of the sensor via the external screw terminal.
Connecting cable terminal assignment
1
2
3
5
6
1
Cable entry for cable on transmitter housing
2
Protective earth (PE)
3
Connecting cable ISEM communication
4
Grounding via ground connection; on device plug versions grounding is through the plug itself
5
Cable entry for cable or connection of device plug on sensor connection housing
6
Protective earth (PE)
Connecting the connecting cable to the sensor connection housing
• Connection via terminals with order code for "Sensor connection housing":
• Option A "Aluminum, coated"→  42
• Option B "Stainless" →  43
• Connection via connectors with order code for "Sensor connection housing":
Option C "Ultra-compact hygienic, stainless"→  44
Connecting the connecting cable to the transmitter
The cable is connected to the transmitter via terminals →  45.
Electrical connection
4
+
B
A
61 62 63 64
61 62 63 64
+
B
A
4
A0028198
41

Advertisement

Table of Contents
loading

Table of Contents