Endress+Hauser Proline Promass E 500 PROFINET Operating Instructions Manual page 156

Coriolis flowmeter
Table of Contents

Advertisement

Commissioning
Parameter
Assign simulation process variable
Process variable value
Status input simulation 1 to n
Input signal level 1 to n
Current input 1 to n simulation
Value current input 1 to n
Current output 1 to n simulation
Value current output 1 to n
156
Parameter overview with brief description
Prerequisite
A process variable is selected
in the Assign simulation
process variable parameter
(→  156).
In the Status input simulation
parameter, the On option is
selected.
In the Current input 1 to n
simulation parameter, the On
option is selected.
In the Current output 1 to n
simulation parameter, the On
option is selected.
Description
Select a process variable for
the simulation process that is
activated.
Enter the simulation value for
the selected process variable.
Switch simulation of the status
input on and off.
Select the signal level for the
simulation of the status input.
Switch simulation of the
current input on and off.
Enter the current value for
simulation.
Switch the simulation of the
current output on and off.
Enter the current value for
simulation.
Proline Promass E 500 PROFINET
Selection / User
Factory setting
entry / User
interface
• Off
Off
• Mass flow
• Volume flow
• Corrected volume
*
flow
*
• Target mass flow
*
• Carrier mass flow
• Target volume
*
flow
• Carrier volume
*
flow
• Target corrected
*
volume flow
• Carrier corrected
*
volume flow
• Density
*
• Reference density
• Reference density
*
alternative
*
• GSV flow
• GSV flow
*
alternative
*
• NSV flow
• NSV flow
*
alternative
*
• S&W volume flow
*
• Water cut
*
• Oil density
*
• Water density
*
• Oil mass flow
*
• Water mass flow
*
• Oil volume flow
• Water volume
*
flow
• Oil corrected
*
volume flow
• Water corrected
*
volume flow
• Temperature
*
• Concentration
Depends on the
0
process variable
selected
• Off
Off
• On
• High
High
• Low
• Off
Off
• On
0 to 22.5 mA
0 mA
• Off
Off
• On
3.59 to 22.5 mA
3.59 mA
Endress+Hauser

Advertisement

Table of Contents
loading