Special Mounting Instructions - Endress+Hauser Proline Promass E 500 PROFINET Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass E 500 PROFINET
Endress+Hauser
 9
Thermal insulation with extended neck free
Heating
NOTICE
Electronics can overheat due to elevated ambient temperature!
Observe maximum permitted ambient temperature for the transmitter .
Depending on the fluid temperature, take the device orientation requirements into
account .
NOTICE
Danger of overheating when heating
Ensure that the temperature at the lower end of the transmitter housing does not
exceed 80 °C (176 °F).
Ensure that sufficient convection takes place at the transmitter neck.
Ensure that a sufficiently large area of the transmitter neck remains exposed. The
uncovered part serves as a radiator and protects the electronics from overheating and
excessive cooling.
When using in potentially explosive atmospheres, observe the information in the
device-specific Ex documentation. For detailed information on the temperature tables,
see the separate document entitled "Safety Instructions" (XA) for the device.
Heating options
If a fluid requires that no heat loss should occur at the sensor, users can avail of the
following heating options:
• Electrical heating, e.g. with electric band heaters
• Via pipes carrying hot water or steam
• Via heating jackets
Vibrations
The high oscillation frequency of the measuring tubes ensures that the correct operation of
the measuring system is not influenced by plant vibrations.
6.1.3

Special mounting instructions

Drainability
The measuring tubes can be completely drained and protected against solids build-up in
vertical orientation.
Sanitary compatibility
When installing in hygienic applications, please refer to the information in the
"Certificates and approvals/hygienic compatibility" section →  278.
Rupture disk
Information that is relevant to the process: →  271.
Installation
A0034391
27