Status
UNCERTAIN - Initial value
UNCERTAIN -
Maintenance demanded
UNCERTAIN - Process
related
GOOD - OK
GOOD - Maintenance
demanded
GOOD - Function check
9.3.4

Factory setting

The slots are already assigned in the automation system for initial commissioning.
Assigned slots
Slot
Factory setting
1
Mass flow
2
Volume flow
3
Corrected volume flow
4
Density
5
Reference density
6
Temperature
7-14
15
Totalizer 1
16
Totalizer 2
17
Totalizer 3
Coding (hex)
Meaning
0x4F
A pre-defined value is output until a correct measured
value is available again or until remedial measures
have been carried out that change this status.
0x68
Signs of wear and tear have been detected on the
measuring device. Short-term maintenance is needed
to ensure that the measuring device remains
operational.
The measured value might be invalid. The use of the
measured value depends on the application.
0x78
The process conditions are not within the device' s
technical specification limits. This could have a
negative impact on the quality and accuracy of the
measured value.
The use of the measured value depends on the
application.
0x80
No error has been diagnosed.
0xA8
The measured value is valid.
It is highly advisable to service the device in the near
future.
0xBC
The measured value is valid.
The measuring device is performing an internal
function check. The function check does not have any
noticeable effect on the process.