Commissioning
Parameter
Terminal number
Assign status input
Active level
Response time status input
118
10.5.7
Configuring the status input
The Status input submenu guides the user systematically through all the parameters that
have to be set for configuring the status input.
Navigation
"Setup" menu → Status input
‣
Status input 1 to n
Assign status input
Terminal number
Active level
Terminal number
Response time status input
Terminal number
Parameter overview with brief description
Description
Shows the terminal numbers used by the
status input module.
Select function for the status input.
Define input signal level at which the
assigned function is triggered.
Define the minimum amount of time the
input signal level must be present before the
selected function is triggered.
10.5.8
Configuring the current output
The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Proline Promass E 500 PROFINET
User interface / Selection /
User entry
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
• Off
• Reset totalizer 1
• Reset totalizer 2
• Reset totalizer 3
• Reset all totalizers
• Flow override
• Zero point adjustment
• High
• Low
5 to 200 ms
→ 118
→ 118
→ 118
→ 118
→ 118
→ 118
Factory setting
–
Off
High
50 ms
Endress+Hauser