Configuring The Totalizer - Endress+Hauser Proline Promass E 500 PROFINET Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass E 500 PROFINET
Parameter
Installation direction
Parameter
Zero point adjustment control
Progress
Endress+Hauser
Parameter overview with brief description
Description
Set sign of flow direction to match the
direction of the arrow on the sensor.
Zero point adjustment
All measuring devices are calibrated in accordance with state-of-the-art technology.
Calibration takes place under reference conditions→  264. Therefore, a zero point
adjustment in the field is generally not required.
Experience shows that zero point adjustment is advisable only in special cases:
• To achieve maximum measuring accuracy even with low flow rates.
• Under extreme process or operating conditions (e.g. very high process temperatures or
very high-viscosity fluids).
Navigation
"Setup" menu → Advanced setup → Sensor adjustment → Zero point adjustment
Zero point adjustment
Zero point adjustment control
Progress
Parameter overview with brief description
Description
Start zero point adjustment.
Shows the progress of the process.
10.6.4

Configuring the totalizer

In the "Totalizer 1 to n" submenu the individual totalizer can be configured.
Navigation
"Setup" menu → Advanced setup → Totalizer 1 to n
Totalizer 1 to n
Assign process variable
Unit totalizer
Totalizer operation mode
Failure mode
Selection
• Flow in arrow direction
• Flow against arrow direction
Selection / User interface
• Cancel
• Start
0 to 100 %
Commissioning
Factory setting
Flow in arrow direction
→  143
→  143
Factory setting
Cancel
→  144
→  144
→  144
→  144