Technical data
258
Damping
Assignable measured
variables
Pulse/frequency/switch output
Function
Version
Maximum input values
Open-circuit voltage
Voltage drop
Pulse output
Maximum input values
Maximum output current
Open-circuit voltage
Pulse width
Maximum pulse rate
Pulse value
Assignable measured
variables
Frequency output
Maximum input values
Maximum output current
Open-circuit voltage
Output frequency
Damping
Pulse/pause ratio
Configurable: 0.07 to 999 s
• Mass flow
• Volume flow
• Corrected volume flow
• Density
• Reference density
• Temperature
• Electronics temperature
• Oscillation frequency 0
• Oscillation damping 0
• Signal asymmetry
• Exciter current 0
The range of options increases if the measuring device has one or more
application packages.
Can be set to pulse, frequency or switch output
Open collector
Can be set to:
• Active
• Passive
• Passive NAMUR
Ex-i, passive
DC 30 V, 250 mA (passive)
DC 28.8 V (active)
For 22.5 mA: ≤ DC 2 V
DC 30 V, 250 mA (passive)
22.5 mA (active)
DC 28.8 V (active)
Configurable: 0.05 to 2 000 ms
10 000 Impulse/s
Adjustable
• Mass flow
• Volume flow
• Corrected volume flow
DC 30 V, 250 mA (passive)
22.5 mA (active)
DC 28.8 V (active)
Adjustable: end value frequency 2 to 10 000 Hz (f
Configurable: 0 to 999 s
1:1
Proline Promass E 500 PROFINET
= 12 500 Hz)
max