Disabling The Web Server - Endress+Hauser Proline Promass E 500 PROFINET Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass E 500 PROFINET
Parameter
Web server functionality
Endress+Hauser
Functions
Meaning
Configuration and checking of all the parameters required for establishing the connection to
Network
the measuring device:
configuration
• Network settings (e.g. IP address, MAC address)
• Device information (e.g. serial number, firmware version)
Logout
End the operation and call up the login page
Navigation area
If a function is selected in the function bar, the submenus of the function open in the
navigation area. The user can now navigate through the menu structure.
Working area
Depending on the selected function and the related submenus, various actions can be
performed in this area:
• Configuring parameters
• Reading measured values
• Calling up help text
• Starting an upload/download
8.4.6

Disabling the Web server

The Web server of the measuring device can be switched on and off as required using the
Web server functionality parameter.
Navigation
"Expert" menu → Communication → Web server
Parameter overview with brief description
Description
Switch the Web server on and off.
Function scope of the "Web server functionality" parameter
Option
Description
Off
• The web server is completely disabled.
• Port 80 is locked.
HTML Off
The HTML version of the web server is not available.
On
• The complete functionality of the web server is available.
• JavaScript is used.
• The password is transferred in an encrypted state.
• Any change to the password is also transferred in an encrypted state.
Enabling the Web server
If the Web server is disabled it can only be re-enabled with the Web server functionality
parameter via the following operating options:
• Via local display
• Via Bedientool "FieldCare"
• Via "DeviceCare" operating tool
Selection
• Off
• HTML Off
• On
Operation options
Factory setting
On