Siemens SINAMICS G115D Operating Instructions Manual page 348

Distributed drive for conveyor applications
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Advanced commissioning
7.31 Activating licensed functions
Activating the license key with Startdrive
Procedure
1. Go online and switch over to the parameter view.
2. In the parameter view, go to parameter p9920
3. Enter the license key (example: "E1MQ-4BEA") - always use uppercase letters:
– p9920[0] = E
– p9920[1] = 1
– ...
– p9920[7] = E
– p9920[8] = A
4. Set p9921 = 1.
After activation, the converter sets p9921 = 0.
You have activated the license key using Startdrive.
Activating the license key with BOP-2
Procedure
1. Convert the license key (example:"E1MQ-4BEA") into decimal numbers based on the table
below.
– E = 69, 1 = 49, M = 77, Q = 81, - = 45, 4 = 52, B = 66, E = 69, A = 65
2. Enter the value in ascending order into p9920
– p9920[0] = 69
– p9920[1] = 49
– ...
– p9920[7] = 69
– p9920[8] = 65
3. Set p9921 = 1.
After activation, the converter sets p9921 = 0.
You have activated the license key using BOP-2.
Converting the license key for input using the BOP-2
Convert the license code into decimal numbers based on the following ASCII table.
346
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA