Siemens SINAMICS G115D Operating Instructions Manual page 427

Distributed drive for conveyor applications
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Precondition
1. The laws for protection from electromagnetic fields in force in individual EU member states
can go beyond the minimum requirements of the EMF Directive 2013/35/EU and always take
precedence.
2. The ICNIRP 2010 limits for the workplace are the basis for the assessment.
3. The 26th BImSchV (German Federal Emission Protection Regulation) defines 100 μT (RMS)
for the assessment of active implants. According to Directive 2013/35/EU, 500 μT (RMS) at
50 Hz is applicable here.
4. Compliance with the limit values was assessed for the following frequencies:
– Line frequency 47 Hz to 63 Hz
– Pulse frequency, for example 4/8/16 kHz and multiples thereof, assessed up to a
5. The routing of power cables has a significant impact on the electromagnetic fields that occur.
Install and operate the components inside metallic cabinets in compliance with the
documentation and use shielded motor cables.
Description
The following information regarding electromagnetic fields relates solely to converters supplied
by Siemens.
The converters are normally used in machines. The assessment and testing is based on DIN
EN 12198.
The indicated minimum distances apply to the head and complete torso of the human body.
Shorter distances are possible for extremities.
 
Minimum distances to
the converter
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
maximum of 100 kHz
EMC installation guidelines (Page 49)
Individuals without active implants Individuals with active implants
Forearm length (approx. 35 cm)
11.5 Protecting persons from electromagnetic fields
Must be separately assessed depend‐
ing on the active implant.
Technical data
425