Advanced commissioning
7.7 Drive control via AS-i
Macro 34, Slave 1 with profile 7.A.5: Converter → control
• p2080[4] = 722.2 State DI2
• p2080[5] = 722.3 State DI3
• Serial data transfer CTT2, four bytes cyclically or acyclically via PIV. The
reading and writing of parameters is possible via the PIV. Because data
is transferred bit-by-bit, the read and write process is very slow.
• Time signal for the CTT2 transfer to the AS-i master
Further information
For more information about the AS-i system, see the AS-Interface - Introduction and Basics
Manual.
7.7.3

Assignment tables

Fixed speeds - Single Slave
Fixed speeds via the motor control bits
AS-i.DO3
178
Cyclic and acyclic communication via CTT2 (Page 180)
 Overview of the manuals (Page 588)
AS-i.DO2
AS-i.DO1
0
0
0
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
1
0
0
1
0
1
1
0
1
1
1
0
1
1
0
1
1
1
1
1
1
AS-i.DO0
Response in the converter
0
OFF1
1
On + fixed speed 1 (factory setting: 1500 rpm)
0
On + fixed speed 2 (factory setting: -1500 rpm)
1
On + fixed speed 3 (factory setting: 300 rpm)
0
On + fixed speed 4 (factory setting: 450 rpm)
1
On + fixed speed 5 (factory setting: 600 rpm)
0
On + fixed speed 6 (factory setting: 750 rpm)
1
On + fixed speed 7 (factory setting: 900 rpm)
0
On + fixed speed 8 (factory setting: 1050 rpm)
1
On + fixed speed 9 (factory setting: 1200 rpm)
0
On + fixed speed 10 (factory setting: 1350 rpm)
1
On + fixed speed 11 (factory setting: 1500 rpm)
0
On + fixed speed 12 (factory setting: 1650 rpm)
1
On + fixed speed 13 (factory setting: 1800 rpm)
0
On + fixed speed 14 (factory setting: 1950 rpm)
1
Acknowledge fault or OFF2
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA