Commissioning
6.4 Quick commissioning
Procedure
1. Open the control panel.
2. Assume master control for the converter.
3. Set the drive to enable state.
4. Switch on the motor.
The converter starts the motor data identification. This measurement can take several
minutes.
Depending on the setting, after motor data identification has been completed, the converter
switches off the motor - or it accelerates it to the currently set setpoint.
5. If required, switch off the motor.
6. Relinquish the master control after the motor data identification.
7. Save the settings in the converter (RAM → EEPROM) (Page 124).
You have completed the motor data identification.
Self-optimization of the speed control
Unexpected machine motion while the motor data identification is in progress
For the stationary measurement, the motor can make several rotations. The rotating
measurement accelerates the motor up to the rated speed. Secure dangerous machine parts
before starting motor data identification:
• Before switching on, ensure that nobody is working on the machine or located within its
• Secure the machine's work area against unintended access.
• Lower suspended loads to the floor.
122
WARNING
working area.
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA