Siemens SINAMICS G115D Operating Instructions Manual page 313

Distributed drive for conveyor applications
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

DC braking when a fault occurs
DC braking initiated by a control command
DC braking when the motor is switched off
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Advanced commissioning
7.21 Electrically braking the motor
Requirement:
Fault number and fault response are assigned
via p2100 and p2101.
Function:
1. A fault occurs, which initiates DC braking as
response.
2. The motor brakes along the down ramp to
the speed for the start of DC braking.
3. DC braking starts.
Requirement:
p1231 = 4 and p1230 = control command, e.g.
p1230 = 722.3 (control command via DI 3)
Function:
1. The higher-level control issues the com‐
mand for DC braking, e.g. using DI3: p1230
= 722.3.
2. DC braking starts.
If the higher-level control withdraws the com‐
mand during DC braking, the converter inter‐
rupts DC braking and the motor accelerates to
its setpoint.
Requirement:
p1231 = 5 or p1230 = 1 and p1231 = 14
Function:
1. The higher-level control switches off the
motor (OFF1 or OFF3).
2. The motor brakes along the down ramp to
the speed for the start of DC braking.
3. DC braking starts.
311

Advertisement

Table of Contents
loading

Table of Contents