Siemens SINAMICS G115D Operating Instructions Manual page 332

Distributed drive for conveyor applications
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

Advanced commissioning
7.27 Monitoring the driven load
Parameters
Parameters
r0031
p2181[0...n]
p2182[0...n]
p2183[0...n]
p2184[0...n]
p2185[0...n]
p2186[0...n]
p2187[0...n]
p2188[0...n]
p2189[0...n]
p2190[0...n]
p2191[0...n]
p2192[0...n]
p2193[0...n]
330
Description
Torque actual value, smoothed
[Nm]
Load monitoring response
Load monitoring speed threshold 1
[rpm]
Load monitoring speed threshold 2
[rpm]
Load monitoring speed threshold 3
[rpm]
Load monitoring torque threshold
1, upper [Nm]
Load monitoring torque threshold
1, lower [Nm]
Load monitoring torque threshold
2, upper [Nm]
Load monitoring torque threshold
2, lower [Nm]
Load monitoring torque threshold
3, upper [Nm]
Load monitoring torque threshold
3, lower [Nm]
Load monitoring torque threshold,
no load [Nm]
Load monitoring delay time [s]
Load monitoring configuration
Setting
Displays the smoothed torque actual value.
Sets the response when evaluating the load moni‐
toring.
0: Load monitoring disabled (factory setting)
1: A07920 for torque too low
2: A07921 for torque too high
3: A07922 for torque outside tolerance
4: F07923 for torque too low
5: F07924 for torque too high
6: F07925 for torque outside tolerance
Sets the speed/torque
envelope curve for load
monitoring.
Sets the torque threshold to identify dry running
operation for pumps or belt breakage for fans.
Factory setting: 0
Sets the delay time to evaluate the load monitoring.
Factory setting: 10
Sets the load monitoring configuration:
0: Monitoring switched off
1: Monitoring torque and load drop (factory set‐
ting)
2: Monitoring speed and load drop
3: Load failure monitoring
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Factory setting: 150
Factory setting: 900
Factory setting: 1500
Factory setting:
10000000
Factory setting: 0
Factory setting:
10000000
Factory setting: 0
Factory setting:
10000000
Factory setting: 0