Siemens SINAMICS G115D Operating Instructions Manual page 335

Distributed drive for conveyor applications
Hide thumbs Also See for SINAMICS G115D:
Table of Contents

Advertisement

You have now set monitoring.
Parameters
Parameters
r0031
p0311[0...n]
r0333[0...n]
p1080[0...n]
p1082[0...n]
p1300[0...n]
p2165[0...n]
p2168[0...n]
p2181[0...n]
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Description
Torque actual value, smoothed
[Nm]
Rated motor speed [rpm]
Rated motor torque [Nm]
Minimum speed [rpm]
Maximum speed [rpm]
Open-loop/closed-loop control op‐
erating mode
Load monitoring blocking monitor‐
ing threshold, upper [rpm]
Load monitoring blocking monitor‐
ing torque threshold [Nm]
Load monitoring response
Advanced commissioning
7.27 Monitoring the driven load
Setting
Displays the smoothed torque actual value.
Sets the rated motor speed.
Factory setting: 0
Displays the rated motor torque.
Sets the lowest possible motor speed.
Factory setting: 0
Sets the highest possible speed.
Factory setting: 1500
Sets the open and closed-loop control mode.
0: U/f control with linear characteristic (factory set‐
ting)
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic characteristic
3: U/f control with parameterizable characteristic
4: U/f control with linear characteristic and ECO
5: U/f control for drives requiring a precise frequen‐
cy (e.g. textiles)
6: U/f control for drives requiring a precise frequen‐
cy and FCC
7: U/f control for a parabolic characteristic and ECO
19: U/f control with independent voltage setpoint
20: Speed control (encoderless)
22: Torque control (encoderless)
Sets the upper speed threshold of the stall moni‐
toring of the pump or fan.
Factory setting: 0
Sets the torque threshold of the stall monitoring of
the pump or fan.
Factory setting: 10000000
Sets the response when evaluating the load moni‐
toring.
0: Load monitoring disabled (factory setting)
7: Pump/fan load monitoring as alarm (A07891,
A07892, A07893)
8: Pump/fan load monitoring as fault (F07894,
F07895, F07896)
333