Number
Cause
A07981
No enabling for rotary measurement Acknowledge pending faults.
A07991
Motor data identification activated
F08501
Setpoint timeout
F08502
Monitoring time sign-of-life expired •
A08511
Receive configuration data not valid •
A08526
No cyclic connection
A08565
Consistency error affecting adjusta‐
ble parameters
F13100
Know-how protection: Copy protec‐
tion error
F13101
Know-how protection: Copy protec‐
tion cannot be activated
F30001
Overcurrent
F30002
DC-link voltage overvoltage
F30003
DC-link voltage undervoltage
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Remedy
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
•
Check the PROFINET connection.
•
Set the controller to RUN mode.
•
If the error occurs repeatedly, check the set monitoring time p2044.
Check the PROFINET connection.
Check the PROFINET configuration
•
Activate the controller with cyclic operation.
•
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
•
IP address, subnet mask or default gateway is not correct.
•
IP address or station name used twice in the network.
•
Station name contains invalid characters.
The know-how protection and the copy protection for the memory card are
active. An error occurred during checking of the memory card.
•
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
•
Deactivate the copy protection (p7765).
Insert a valid memory card.
Check the following:
•
Motor data, if required, carry out commissioning
•
Motor connection method (Υ / Δ)
•
U/f operation: Assignment of rated currents of motor and Power Module
•
Line quality
•
Power cable connections
•
Power cables for short-circuit or ground fault
•
Power cable length
•
Line phases
If this doesn't help:
•
U/f operation: Increase the acceleration ramp
•
Reduce the load
•
Replace the power unit
Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Check the line voltage (p0210).
Alarms, faults and system messages
9.6 List of alarms and faults
385