Function description
Example
Setting with the motorized potentiometer as setpoint source:
Parameter
p1070 = 1050
Parameters
Table 7-4
Parameter
p1035[0...n]
p1036[0...n]
p1040[0...n]
p1047
p1048
r1050
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Description
Interconnects the main setpoint with the motorized potentiometer output.
Basic settings
Description
BI: Motorized potentiometer set‐
point higher
BI: Motorized potentiometer set‐
point lower
Motorized potentiometer start val‐
ue [rpm]
Motorized potentiometer, ramp-up
time [s]
Motorized potentiometer, ramp-
down time [s]
Motorized potentiometer, setpoint
after the ramp-function generator
Advanced commissioning
Setting
Signal source to continuously increase the setpoint
The factory setting depends on the converter.
With PROFINET interface: [0] 2090.13; [1] 0
Without PROFINET interface: 0
Signal source to continuously decrease the setpoint
The factory setting depends on the converter.
With PROFINET interface: [0] 2090.14; [1] 0
Without PROFINET interface: 0
Start value that is effective when the motor is
switched on.
Factory setting: 0 rpm
MOP ramp-up time
Factory setting: 10 s
MOP ramp-down time
Factory setting: 10 s
Motorized potentiometer, setpoint after the ramp-
function generator
7.17 Setpoints