This device must be used in an overvoltage category II installation only.
If your unit does not have a circuit breaker, install and operate it with an AE-approved
circuit breaker on the ac input to provide the required over-current protection.
To connect your system to the power supply, you need stranded wire of a gauge consistent
with your application and applicable requirements. To connect to the power supply's input
power connector, follow these steps:
1. Strip approximately 60 to 70 mm of the insulation from the end of the power cord.
2. Separate the five wires and strip approximately 10 mm of the insulation from each wire.
3. Ensure that the ground wire (the yellow and green wire) is approximately 7 mm longer
than the other wires.
4. Remove the cover from the strain relief.
5. Slip the cable through the cord grip.
6. Connect each wire to the proper input terminal block according to the labels. Tighten the
cable clamp on the line cord, and replace the cover.
Note: Use only a shielded input cable on the input power connector.
5702199-A
Page 137 of 182
Installation
Pinnacle™ 20 kW
5-9