Quantum DXi6900 Field Service Manual page 126

With dxi 3.4.0 software
Hide thumbs Also See for DXi6900:
Table of Contents

Advertisement

Chapter 3: FRU Removal and Replacement Procedures
Replacing Node Cooling Fans
100
Caution: Use appropriate ESD precautions, including the use of a
grounding strap, when performing this procedure.
Removing and replacing a cooling fan in the Node includes the
following steps:
Identifying a Failed Cooling Fan in the Node
Removing a Failed Cooling Fan from the Node
Installing a Replacement Cooling Fan in the Node
Identifying a Failed Cooling Fan in the Node
The DXi6900 G1 Node contains six cooling fans that provide cooling for
the processors, expansion cards, and memory modules.
To identify the failed cooling fan:
1 Access the remote management console (see
Management
on page 25).
2 Navigate to the Status > Hardware > Details > System Board
page.
3 Note the number (1–6) of the cooling fan that has a Failed status
(see
Figure
54).
Accessing Remote
Quantum DXi6900 G1 User's Guide