YASKAWA DX200 Maintenance Manual page 1093

Hide thumbs Also See for DX200:
Table of Contents

Advertisement

Alarm Name
Alarm
Sub
Number
Code
2
3
4
5
6
7
Meaning
Cause
other
Brake slip detection could not
Software operation error
be executed in the specified
occurred
axis.
Holding torque data which is
Software operation error
calculated by the brake slip
occurred
detection is incorrect.
Detection torque data which is
Software operation error
calculated by the brake slip
occurred
detection is incorrect.
The torque value for the brake
Software operation error
slip detection device is not
occurred
set.
other
Holding torque data which is
Software operation error
calculated by the brake slip
occurred
detection exceeds the limit.
other
The parameter of the pulse
Software operation error
operation exceeds the limit.
occurred
other
Remedy
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
(1)Reset the alarm. (2)Check the following settings.
Check torque value
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Reset the alarm. (2)Check the following settings.
Check torque value
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Reset the alarm. (2)Check the following settings.
Pulse operation (S1CxG512 to 519)
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).