Alarm Name
Alarm
Sub
Number
Code
4615
I/O AXIS OPERATING
4616
AXIS SHIFT ERROR
1
2
3
4617
S/U IMPOSSIBLE
1
MOVE (L/R POS)
Meaning
Cause
other
An attempt was made to
Setting error
command a job whose control
group was in I/O axis motion.
other
The file could not be switched
Software operation error
because of incorrect start
occurred
point designation.
The control group with which
Software operation error
the axis shifting is performed
occurred
disagrees with the control
group set for the axis shifting
function in the calibration file.
The calibration file number for
Setting error
axis shifting function is out of
the applicable range.
other
For the CSL15D manipulator,
Setting error
the motion speed of S- and U-
axes exceeded the upper
limit.
Remedy
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Does not the I/O axis motion executed for the control group that
executing the job?
Does not the job executed for the control group that operating by the
I/O axis motion?
The control group where the I/O axis is operating cannot execute the
job. Moreover, the I/O axis motion cannot perform for the control group
where the job is executing.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Check the following settings.
Correct the settings for the OPTON instruction tag so that value of the
file number specification is 1 to 32.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Reduce the teaching speed of S- and U-axes.
Teach the positions of L- and R-axes again so that S- and U-axes can
move.