Alarm Name
Alarm
Sub
Number
Code
16
17
18
19
4611
OVER OPTON INST
EXECUTION LIMIT
4612
TSYNC ERROR
4613
SERVO SEALER GUN
1
CONTROL ERROR
Meaning
Cause
Memoplay debug error
Software operation error
C_BANK RT_BANK.func_ctrl
occurred
(continue)
Memoplay debug error MOVL,
Software operation error
MOVC (continue)
occurred
Memoplay debug error Same
Software operation error
point, moving amount is zero
occurred
(continue)
Memoplay debug error
Software operation error
Dividing number error
occurred
Setting error
other
Sub code: the number of
Setting error
synchronizations of the first
executed TSYNC
other
The function designation
Setting error
parameter is not set.
other
Remedy
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Check the following settings.
Check the settings for the OPTON instruction. OPTON instruction can
use only the function to five simultaneously.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Check the settings for the number of synchronizations of the TSYNC
instruction.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Check the settings for the function designation parameter.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).