Alarm Name
Alarm
Sub
Number
Code
4523
SHARED AXES
1
CONTROL ERROR
4524
CANNOT EXECUTE
INST(CONCUR JOB)
4525
CANNOT EXECUTE
1
SPECIFIED JOB
2
3
4527
UNDEFINED PORT
NO.(AOUT)
Meaning
Cause
The teaching points are
Software operation error
incorrect.
occurred
Setting error
other
An interrupt job (user setting)
Setting error
is started up during the back
operation.
other
An suspend macro job is
Setting error
started up during the back
operation.
other
An interrupt job (inside the
Setting error
system) is started up during
the back operation.
other
Setting error
other
Remedy
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Check the following settings.
Delete an instruction that cannot be executed such as move
instruction in the concurrent job.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Check the job so that the interrupt job will not start-up during the back
operation.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Check the job so that the suspend macro job will not start-up during
the back operation.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Check the job so that the interrupt job will not start-up during the back
operation.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Check the settings for the specified analog output port number.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).