Alarm Name
Alarm
Sub
Number
Code
9
10
11
12
Meaning
Cause
Zero or a negative value is set
Setting error
in the maximum diameter
parameter (S1CxG064) for the
Form Cutting motion.
other
Although "PLACEMENT" or
Setting error
"AUTO" is set for the start
point designation on the
FORM CUT SETTING
window, the FORMAPR
instruction was not executed.
other
The Cut file setting of the
Setting error
FORMAPR instruction is
different from that of the
FORMCUT instruction.
other
A FORMAPR instruction was
Setting error
used for the conventional
FORMCUT instruction.
other
Remedy
(1)Check the following settings.
The setting of the maximum diameter parameter (S1CxG063) for the
Form Cutting motion.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
Execute the FORMAPR instruction.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
The Cut file settings of FORMAPR and FORMCUT instructions must
be same.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Check the following settings.
The FORMAPR instruction cannot be used for the conventional
FORMCUT instruction.
Validate the new FORMCUT instruction.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).