Alarm Name
Alarm
Sub
Number
Code
4699
SYSTEM ERROR 1
(RSC1)
4700
SYSTEM ERROR 2
(RSC1)
4701
MEMORY
ALLOCATION ERROR
4703
F-SAFE OPERATION
MODE ERROR
4707
TIMING CONTROL
1
ERROR
2
3
Meaning
Cause
Sub Code
Software operation error
Internal control error in
occurred
software
Sub Code
Software operation error
Internal control error in
occurred
software
Software operation error
occurred
Data error
YSF25 board failure
other
Control data error occurred at
Software operation error
pre-reading. (Function the
occurred
timing control)
Control data error occurred.
Software operation error
(Function the timing control)
occurred
Index number of the target
Software operation error
does not exist.
occurred
(Function the timing control)
Remedy
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Change the teach mode.
(2)Reset the alarm, and then try again.
(3)If the alarm occurs again, set to home position.
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the YSF25 board. Save the
CMOS.BIN before replace the unit to be safe.
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
(1)Reset the alarm, and then try again.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).