Bulk Output Module
A fuse alarm input for monitoring an external distribution is available on the Bulk Output Module on
connector J3, pin 1 (Figure 6-3).
The input can be connected to a relay which provides system voltage on alarm. Pin 2 (V-) can be used to
provide system voltage with a clean relay contact.
Bulk Output Module

Additional Bulk Output Module Connections

Vsense-, Vsense+
Pins 1 and 2 (Vsense- and Vsense+) on J2 are wired to monitor system voltage internal to the Bulk Out-
put Module. To monitor system voltage externally, unplug the mating connector from J2 and connect
Vsense- and Vsense+ to the external source to be monitored.
Page 81
© Copyright 2021 ABB. All rights reserved.
J3
J2
Figure 6-3: Bulk Output Module Connectors