ABB CPS6000 Product Manual page 92

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Installed Capacity
On-Line Capacity
Current
Number Of Strings
Highest Temp
Temp Probes
Mid-Cell Volts
Battery Test Result
Next Test
Live Reserve Time
Shunt Currents: A maximum of six measured currents from each Distribution Control and Monitoring
module present in the system is displayed.
Disconnect States: The status of the LVBD (Low Voltage Battery Disconnect) and LVLD1-3 (Low Voltage
Load) disconnects are displayed. "None" is displayed if there are no contactors in the system.
Alarm Thresholds: Present alarm threshold settings in xx.xV format of the following system alarms:
Float Voltage Alarms
Boost Voltage Alarms
High Batt Temp
Reserve Low
High Ambient Temp
Low Ambient Temp
Ringer Thresholds: Present status of up to two ringer chassis:
State
VA
Primary
Secondary
Enable-Disable Info: Displays the enable/disable status of the following features:
Temp Comp
Low Temp Comp
Recharge Ilim
Auto Boost
Auto Batt Test
Rect Redund
Mid-Cell V Mon
Imminent Shutdn
Local Write
Modem Write
Page 92
© Copyright 2021 ABB. All rights reserved.
User entered system battery capacity in AH. Automatically entered when using smart Lithium
batteries.
Available battery reserve from installed capacity value directly connected to the bus. It is
always the same value configured for installed capacity except for when the smart lithium
batteries are utilized.
Current flowing into or out of the batteries.
The total number of battery strings installed in the system.
Highest battery temperature being measured by the thermal probes.
Number of installed thermal probes.
Number of installed Mid-cell voltage measurement modules.
Shows whether the most recent battery test was completed, and the reserve time.
The date of the next automatic battery discharge test. The automatic
discharge test feature must be enabled for this to work.
Present value of battery reserve time calculated by the controller
Very High Major, Very High Minor, BD Major and Very Low major
Very High Major and High Minor
Highest temperature being measured by the thermal probes
Low battery reserve time
High ambient temperature
Low ambient temperature
Ringer chassis present or not
Output VA of ringer
Ringer module present in primary position
Ringer module present in secondary/redundant position
Temperature compensation
Low temperature compensation
Recharge current limit
Automatic boost charge
Automatic battery test
Rectifier redundancy
Mid-cell voltage monitoring
Imminent system shutdown alarm (LVBD)
Whether or not the system can be configured through the local port.
Whether or not the system can be configured through the modem port.