ABB CPS6000 Product Manual page 168

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Description
This command reports the boost history in the following format: sum bs1,stt
30-MAY-03,15:11:12,RESUMED,COMPLETED,78
30-MAY-03,12:03:34,AUTO,DISCHARGE,14
.
**
This report gives the start date, start time, start reason, stop reason, and boost duration in minutes.
The start reasons are:
MANUALBoost initiated by user
AUTOBoost started automatically after a battery discharge
RESUMEDBoost resumed after being suspended by a discharge
The stop reasons are:
COMPLETEDBoost completed normally
TIMEOUTBoost timed out before completing
DISCHARGEBoost suspended because of a battery discharge
CANCELEDBoost canceled by user
ALARMBoost cancelled by an alarm condition
DISABLEDAuto boost cancelled by being disabled
his
Report BD history
Syntax:
dc1,bod
Description
This command reports the battery discharge history in the following format: his dc1,bod
30-MAY-03,15:11:12,MANUAL,COMPLETED,118.3,23,
01-APR-03,03:11:12,BD,COMPLETED,118.3,26,130
12-FEB-03,12:00:02,PERIODIC,COMPLETED,120.9,27,135
.
**
This report gives the start date, start time, start reason, current at start of discharge, duration in
minutes, and, if calculated, a reserve time prediction. The start reasons are:
MANUALDischarge test initiated by user
PERIODICPeriodic discharge test
BDNatural battery discharge
The stop reasons are:
Page 168