Nominal Output Voltage
Operating Output Voltage Ranges
Boost Voltage
Output Current
Nominal Input Voltage
Input Voltage Ranges
Input Current
Operating Frequency Range
Operating Temperature
Output Voltage Regulation
Output Noise, Ripple
Load Share Accuracy
Heat Dissipation (per rectifier, full load)
Power Factor
Selective High-Voltage Shutdown
Backup High-Voltage Shutdown
Nominal Output Voltage
Operating Output Voltage Ranges
Boost Voltage
Output Current
Nominal Input Voltage
Input Voltage Ranges
Input Current
Operating Frequency Range
Operating Temperature
Output Voltage Regulation
Output Noise, Ripple
Load Share Accuracy
Heat Dissipation (per rectifier, full load)
Power Factor
Selective High-Voltage Shutdown
Backup High-Voltage Shutdown
Page 20
© Copyright 2021 ABB. All rights reserved.
48/52/54.5 V
42 to 58 V
48 to 58 V
0 to 40A at 54.5V
200/208/240 V
150 to 275 V
11.8A at 208 V
45 to 66 Hz
-40 to +75 °C
±0.5%
250 millivolts peak to peak maximum, over the range dc to
100 MHz
1.5A maximum deviation between rectifiers
240W (819 BTU) at 240 V
>0.98 for loads > 50% full load
Above 58 V
Above 60 V
Table 2-H: QS864A Rectifier Specifications (Preliminary)
48/52/54.5 V
42 to 58 V
48 to 58 V
0 to 50A at 54.5V
200/208/240 V
150 to 275 V
14.5A at 208 V
45 to 66 Hz
-40 to +65 °C
±0.5%
250 millivolts peak to peak maximum, over the range dc to 100
MHz
1.5A maximum deviation between rectifiers
267W (911 BTU) at 240 V
>0.98 for loads > 50% full load
Above 58 V
Above 60 V
Table 2-I: QS865A Rectifier Specifications
dc
dc
dc
ac
ac
ac
operation
ac
dc
for 1 millisecond
dc
dc
dc
dc
ac
ac
ac
operation
ac
dc
for 1 millisecond
dc