ABB CPS6000 Product Manual page 101

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

PIN
The QS841A has the ability to restrict certain access from the front panel of the unit. It incorporates a
four-digit Power Identification Number (PIN) on the front panel for certain control/operations and
configurable items. The default PIN password is 0000. Each position of the password is configurable
between 0-9. The password can be configured from the remote interfaces by a user with Administrator
privileges. The front panel PIN feature can be Enabled or Disabled through the remote interface by a
user with Administrator privileges.
Factory default for PIN operation in the standard QS840A is Disabled.
If the PIN feature is enabled, the PIN is required for items that generally are not functions of a typical
maintenance routine. It is assumed that the majority of the configured thresholds and system
operational features will not be changed through a maintenance routine. Thus, they require entrance of
the correct PIN in order for the parameter or feature to be modified in the field. There are some
Control/Operations that also require the PIN shown below.
1.
Clear History
2.
Clear Statistics
3.
Disconnects – Manual disconnect/reconnect of any LVLD/LVBD
4. Enter Boost
Other Control/Operations features listed below do not require PIN access.
1.
Lamp Test
2.
Restart Rectifiers
3.
Uninstall Equipment
4. Start Battery Test
5.
Start Alarm Test
6. Load Factory Defaults
All configuration items from the front panel require PIN access except for the following:
1.
Battery Type
2.
String Battery Capacity (AH)
3.
Number Of Battery Strings
4. Manual Discharge Test Type
5.
Manual Test Duration
6. Manual Test Check Battery Alarm Voltage Threshold
7.
Battery Test Rectifier Voltage
8. System Date Format
9. System Date
10. System Time Format
11. System Time
12. Automatic Daylight Savings Feature
13. Display Contrast
14. Temperature Display Units
15. Alarm Test Feature
16. Alarm Test Relay Duration and Relay
Page 101
© Copyright 2021 ABB. All rights reserved.