ABB CPS6000 Product Manual page 110

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Clear History
Clear Statistics
Alarm Test
Start Battery Test
Disconnects
Enter Boost Mode
Load Factory Defaults
Reset Passwords
Clear History
This area of the menu system contains event history information. The controller works on a first record
in first record out once the record size of a specific field is reached. The following system history logs
are available:
Alarm History
BD History
Boost History
Rectifier History
Page 110
© Copyright 2021 ABB. All rights reserved.
This area of the menus system can be used to clear the various items that the controller
maintains history records. Once cleared the controller begins to keep history of new events.
Alarm History
Operation to only clear alarm event history.
BD History
Operation to only clear BD network access history.
Rectifier History
Operation to only clear rectifier event history.
Boost History
Operation to only clear Boost event history.
Local Port History Operation to only clear local port access history.
Modem History
Operation to only clear Modem port access history.
Network History
Operation to only clear network access history.
All History
Allows a single command operation to clear all history
records from the QS841.
This area of the menus system can be used to clear the various items that the controller
maintains statistical records. Once cleared the controller begins to keep new statistical
data.
Clear Basic - This operation allows the user to clear individually or as a group the Basic
statistical data kept on Plant Load, the highest battery temperature, and ambient.
Clear Trend - This operation allows the user to clear the trend data kept on the plant load.
Clear BD - This operation allows the user to clear the Battery on Discharge (BD) statistics
kept on the plant load and voltage during discharge.
Initiates the Form-C alarm test by asserting each of the configured Form-C alarms at the
configured alarm interval.
Initiates the manual battery test feature. A stop battery test operation is displayed to
interrupt the testing and return the unit to normal operation. The manual battery test utilizes
the configured test duration and a system bus voltage threshold to represent the end of
reserve.
Provides individual manual control of the four Low Voltage Disconnects
(LVBD, LVLD1-3) for maintenance purposes.
Initiates the manual battery Boos feature. A stop battery Boost operation is displayed to
interrupt the Boost operation mode and return the unit to normal operation.
This operation allows a user to bring back all factory defaults with a single operation. Caution
should be used when applying this command. Previous configuration changes will be
overwritten.
Resets user, super-user and administrator passwords back to standard defaults.
Chronological view of the last 256 alarms and events that have occurred since the last time
the history log was cleared.
Chronological view of the last 16 battery on discharge (BD) events since the last time the
history log was cleared.
Chronological view of the last 16 times the system entered boost mode since the last time the
history log was cleared.
Chronological view of the last 256 rectifier alarms and events that have occurred since the last
time the history log was cleared.