The line ":DC1 ADC" indicates that the information that follows is for the plant load current. The "HHI="
indicates highest hourly instantaneous reading. The "LHI=" indicates highest hourly instantaneous
reading. The "HHA=" indicates highest hourly average reading. The "." line is the end-of-command
identifier. The "* " in the example above is the user command line prompt.
sum
Report Plant Load Trend Statistics
Syntax:
sum dct1
Description
This command reports the plant trend statistics, which includes up to 16 daily highest hourly and
lowest hourly instantaneous readings, up to 32 daily maximum hourly averages, and up to 13 monthly
averages of the daily maximum hourly averages. The following is an example of a command response:
* sum dct1
:DCT1 SRC=DC1 ADC
CLR=01-JAN-2001,12:00:00 DHI=
29-JAN-2002,02:00;00,123.2
30-JAN-2003,05:00:00,120.1
31-JAN-2003,14:00:00,122.8 DLI=
29-JAN-2002,12:00;00,120.9
30-JAN-2003,08:00:00,118.7
31-JAN-2003,01:00:00,119.2 DHH=
29-JAN-2002,02:00;00,122.1
30-JAN-2003,05:00:00,119.7
31-JAN-2003,14:00:00,121.6 MAV=
31-JAN-2003,23:00:00,121.3
.
*
The "DHI=" indicates daily highest hourly instantaneous reading. The "DLI=" indicates daily highest
hourly instantaneous reading. The "DHH=" indicates daily highest hourly average reading. The "MAV="
indicates monthly average of daily highest hourly average reading. The "." line is the end-of-command
identifier. The "* " in the example above is the user command line prompt.