ABB CPS6000 Product Manual page 76

-48v indoor/outdoor power shelf
Hide thumbs Also See for CPS6000:
Table of Contents

Advertisement

Step
Action
Typing HELP at the "$" will show all available network administration commands and command line
formats.
*note: 1) commands are not case sensitive
2) for the commands that follow, ddd is a number from 0 – 255
To set the IP Address, type:
CHA NET1,IP=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,IP
To set the Subnet mask, type:
CHA NET1,SUB=ddd.ddd.ddd.ddd
Verify by typing:
8A
STA NET1,SUB
Optional:
To set the Default Gateway Address, type:
CHA NET1,GTWY=ddd.ddd.ddd.ddd
Verify by typing:
STA NET1,GTWY
Optional:
To set the Host Name, type:
CHA NET1,HOST="hostname"
Verify by typing:
STA NET1,HOST
Logging out of the QS841A MCU.
To terminate the configuration session, enter the "bye" command. The QS841A will notify the user if
configuration is not complete. This message will have the following format:
NOTICE:
Default Gateway may be required for network access. Host Name may be required for network access.
8B
Logging off...
Messages referencing the Gateway and Host Name are acceptable, since the se parameters are optional.
Note: If the IP address or Subnet mask messages appear, for example: IP Address is required for network
access.
Subnet mask is required for network access.
Then the configuration procedure must be repeated.
Post Installation Procedure.
Once configuration has been completed
Disconnect the PC from the QS841A local port (RS-232) connector J3.
8C
After approximately one minute, observe the LEDs on the J3 net work connector:
Green - STATUS LED: ON
Yellow - Link / Active LED: ON
The QS841A should be communicating over the network.
Page 76