Alarm Thresholds/Relays
obj,attr
description
bda1,acc
Battery on discharge relay
bda1,ast
Battery on discharge alarm state
bda1,sev
Battery on discharge severity
bda1,thr
Battery on discharge threshold
bta1,acc
High battery temperature relay
bta1,ast
High batt temperature alarm state
bta1,sev
High battery temperature severity
bta1,thr
High battery temperature
hfv1,acc
High voltage relay
hfv1,ast
High voltage alarm state
hfv1,bth
High boost voltage threshold
hfv1,fth
High float voltage threshold
hfv1,sev
High voltage severity
hva1,acc
Very high voltage relay
hva1,ast
Very high voltage alarm state
hva1,bth
Very high boost voltage threshold
hva1,fth
Very high float voltage threshold
hva1,sev
Very high voltage severity
rtl1,acc
Reserve time low relay
rtl1,ast
Reserve time low alarm state
rtl1,sev
Reserve time low severity
rtll,thr
Reserve time low threshold
vla1,acc
Very low voltage relay
vla1,ast
Very low voltage alarm state
vla1,sev
Very low voltage severity
vla1,thr
Very low voltage threshold
amtl1,acc
Low ambient temp relay
amtl1,ast
Low ambient temp alarm state
amtl1,sev
Low ambient temp severity
amtl1,thr
Low ambient temp threshold
amth1,acc
High ambient temp relay
amth1,ast
High ambient temp alarm state
amth1,sev
High ambient temp severity
amth1,thr
High ambient temp threshold
acf1,acc
AC fail relay
acf1,ast
AC fail alarm state
acf1,sev
AC fail severity
Page 158
© Copyright 2021 ABB. All rights reserved.
Related Commands
sta
cha
ope
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
type
range of values
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ","MIN" , or "RO"
number
46-55:51V
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
number
30-85:55C
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
number
50-60:56V
number
50-60:56V
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
number
50-60:57V
number
50-60:57V
text
"MAJ", "MIN" , or "RO"
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
number
0-99.9 hours
text
"R1" ,"R2", "R3", R4, or ""
number
0:not active 1:active
text
"MAJ","MIN" , or "RO"
number
40-51:46V
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
number
-40-10:-40C
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"
number
35-75:75C
text
"R1" ,"R2", "R3", "R4", or ""
number
0:not active 1:active
text
"MAJ", "MIN" , or "RO"

Advertisement